11

ArmorBlock 2 Input/2 Output Module

Publication 1792-5.5 – October 1996

Bit

07

06

05

04

03

02

01

00

Produces

IS

Reserved

OF1

OF0

I1

I0

Consumes

Reserved

O1

O0

Where: I = Input

IS = Sensor source voltage fault
O = Output
OF = Output fault

Word

Bit

Description

Produces

00–01

Input bits – bit 00 corresponds to input 0, bit 01 to input 1. When the
bit is set (1), the input is on.

02–03

Output fault bits – Shows fault status of each output. OS0
corresponds to output 0, and OS1 corresponds to output 1. When
the bit is set (1), the output is faulted.

04–06

Reserved

07

Sensor source voltage fault bit – this bit is set (1) when the sensor
source voltage is faulted.

Consumes 00–01

Output bits – Bit 00 corresponds to output 0, bit 01 corresponds to
output 1. 0 = output off; 1 = output on

02–07

Reserved

Configure Your Armor

Block Module Offline Using the

DeviceNet Manager Configuration Tool

To configure your ArmorBlock module offline:

add the device to the network

set the parameters for the device

save the parameters to a file

Note: You cannot actually configure your device offline. You can set
and save the parameters to a file for downloading to the device when
you go online.