ArmorBlock 2 Input/2 Output Module

Publication 1792-5.5 – October 1996

Connecting the Input Wiring

Connect input wiring to the micro connectors which screw into mating
connectors on the side of the block.

Make connections as shown below.

1

2

3

4

I/O Input Micro Connector

Pin 1 = Sensor Source Voltage Positive

Pin 3 = Negative/Return

Pin 4 = Signal

(View into socket)

Pin 2 = Not used

Connecting the Output Wiring

Connect individual output wiring to micro connectors which screw into
mating connectors on the side of the block. Make connections as shown
below.

1

2

3

4

I/O Output Micro Connector

Pin 1 = Not used

Pin 2 = Not used

Pin 3 = Negative

Pin 4 = Output

(View into socket)

Connect the output power wiring to the 3-pin mini connector on the end
of the block.

Important:

The outputs use electronic overcurrent fault protection. Make certain
your output power supply can handle overcurrent events.

1

2

3

Output Power Mini Connector

Pin 1 = Not used

Pin 2 = Positive

Pin 3 = Negative

(View into pins)