ArmorBlock 2 Input/2 Output Module

Publication 1792-5.5 – October 1996

Reset Faults using Explicit Message Program Control

You can also reset inputs and outputs using the Explicit Message
Program Control feature on the Scanner module master. Refer to the
specific scanner publications for information on using this feature.

The format for the reset explicit message transaction block must
contain 6 words as shown below:

Word

Input Fault

Output Fault

Transaction
Header

Word 0

TXID – CMD/STATUS

TXID – CMD/STATUS

Header

Word 1

PORT – SIZE

PORT – SIZE

Word 2

Service = 32 hex – MAC ID

Service = 32 hex – MAC ID

Transaction
Body

Word 3

Class = 1D hex

Class = 9

Body

Word 4

Instance = 1

Instance = n – where n = number
of the output (1 or 2)

Word 5

Attribut Data = 0

Attribut Data = 0

Configure Your Armor

Block Module Using EDS Files

Current versions of DeviceNet Manager software include ArmorBlock
module support. If you are using a version of DeviceNet Manager
software that does not include ArmorBlock module Electronic Data
Sheets (EDS) files in its library, you can use the following information
to create the file.

If you are using a configuration tool other than DeviceNet Manager,
you can also use the following information to create the EDS file.
(Note: This EDS file was current at the time of printing. Contact your
nearest district office for information on later files.)

$ Electronic Data Sheet for Armor Block I/O (1792–IB2XOB2E)
[File]
DescText = ”1792–IB2XOB2E Armor Block I/O EDS File”;
CreateDate = 04–18–96;
CreateTime = 12:00:00;
ModDate = 09–17–96;
ModTime = 16:00:00;
Revision = 2.1;

$ EDS revision.

[Device]
VendCode = 1;