Produce and Consume a Tag Chapter 1

10. Click the Status tab to configure the status properties for the consumed

tags.

11. In the Data Type list, click the data type that allows the connection status.

12. Click OK.

Note:

If you consume the tag over a ControlNet network, use RSNetWorx for ControlNet software to schedule the network.

Additional steps for a PLC-5C controller

If you are sharing data with a PLC-5C controller, do the following.

Action

Details

In the ControlNet configuration of the
PLC-5C controller, schedule a message.

If the PLC-5C

controller

This

Then in RSNetWorx software

Produces

Integers

In the ControlNet configuration of the PLC-5C controller, insert a Send Scheduled
Message.

Consumes

Integers

Do these steps in the ControlNet configuration of the PLC-5C controller.
Insert a Receive Scheduled Message.
In the Message size, enter the number of integers in the produced tag.

REALs

Do these steps in the ControlNet configuration of the PLC-5C controller.
Insert a Receive Scheduled Message.
In the Message size, enter two times the number of REALs in the produced tag. For

example, if the produced tag contains
10 REALs, enter 20 for the Message size.

Rockwell Automation Publication 1756-PM011F-EN-P - October 2014