Produce and Consume a Tag Chapter 1

Scenario 3

The RPI is outside the range of the producing controller’s RPI Limits. A default

RPI is set up for the producing controller. But, the network path contains a bridge

that blocks the negotiated RPI to prevent an interruption to other controllers on

the network.

Version 17 and earlier: The RPI requested by the consumed tag is not within the

range of the producer. The connection is rejected and a 0112 error is reported that

the connection failed. You must re-enter an RPI that is within the range

configured on the produced tag. If a version 17 consumer is trying to connect with

a version 18 producer and the RPI is outside the range of the producer, a 0112

error reports the connection failed.

Tip:

See

RPI I/O Faults

on

page

30

for an explanation of the error messages.

Version 18 and later: The RPI requested by the consumed tag is not within the

RPI limitation range of the producer. The producer is configured to provide an

RPI default. The producer sends the default RPI to the consumer, but the

consumer controller is not set up to accept a default RPI from the producer. The

negotiated RPI is disabled to prevent an interruption to the multicast connection.

A 0112 error message is reported and you must re-enter an RPI within the range of

the producer’s limits.