The RPI is outside the range of the producing controller’s RPI Limits.

There is no default RPI that is set up for the producing controller.

Version 17 and earlier: The RPI requested by the consumed tag is not within the

range of the producer. The connection is rejected and a 0111 error is reported that

the connection failed. You must re-enter an RPI that is within the range

configured on the produced tag. If a version 17 consumer is trying to connect with

a version 18 producer and the RPI is outside the range of the producer and there is

no default set up, a 0111 error reports the connection failed.

Tip:

See

RPI I/O Faults

on

page

30

for an explanation of the error messages.

Version 18 and later: The RPI requested by the consumed tag is not within the

RPI limitation range of the producer. The producer is not set up to provide a

default RPI, so a 0111 error message is reported that the connection failed. You

must re-enter an RPI that is within the range configured for the producer because

there is no RPI default negotiation with the consumer.