Verify consumed tag acceptance – Rockwell Automation Logix5000 Controllers Produced and Consumed Tags Programming Manual User Manual

Page 22

Advertising
background image

Chapter 1 Produce and Consume a Tag

Important:

The check box that activates ’RPI Provided by Producer’ is disabled online. This check box must be

checked for the RPI negotiation to succeed. If the check box is not checked, the consuming
controller does not accept the RPI provided by the producer if the consuming controller requests
an RPI that is out of the producer’s configured RPI range. As a result, an out-of-range RPI request
results in a failed connection.

When a consuming controller accepts a default RPI by a producing controller, you

can verify the acceptance and the RPI value on the Consumed Tag Connection

dialog box. You must be online to complete the following procedures.

1. Open the Logix Designer application and choose a controller that is set up

with a consuming tag.

2. In the Controller Organizer, right-click the Controller Tags folder and

choose Edit Tags.

3. In the Controller Tags window, right-click a consuming tag and choose

Edit (name of tag) Properties.

Verify consumed tag
acceptance

22

Rockwell Automation Publication 1756-PM011F-EN-P - October 2014

Advertising