Important:
The check box that activates ’RPI Provided by Producer’ is disabled online. This check box must be
checked for the RPI negotiation to succeed. If the check box is not checked, the consuming
controller does not accept the RPI provided by the producer if the consuming controller requests
an RPI that is out of the producer’s configured RPI range. As a result, an out-of-range RPI request
results in a failed connection.
When a consuming controller accepts a default RPI by a producing controller, you
can verify the acceptance and the RPI value on the Consumed Tag Connection
dialog box. You must be online to complete the following procedures.
1. Open the Logix Designer application and choose a controller that is set up
with a consuming tag.
2. In the Controller Organizer, right-click the Controller Tags folder and
choose Edit Tags.
3. In the Controller Tags window, right-click a consuming tag and choose
Edit (name of tag) Properties.
Verify consumed tag
acceptance
22