Rockwell Automation 1790P-T8BV8B Profibus DP Digital Base Terminal Block Compact Block LDX I/O I.I. User Manual

Page 13

Advertising
background image

13

Publication 1790-IN009B-EN-P - April 2003

PROFIBUS DP Digital Base Terminal Block Specifications

The following table contains specifications that are common to
all of the base blocks in this document. Individual base block
specifications are detailed after this table.

Environmental Specifications

Operating Temperature 0 to 55°C (32 to 131°F)

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

Storage Temperature

-40 to 85°C (-40 to 185°F)

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock)

Relative Humidity

5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)

Operating Altitude

2000m

Vibration

I2g @ 10-500Hz
EC60068-2-6 (Test Fc, Operating)

Shock: Operating
Non-operating

I0g
30g
IEC60068-2-27 (Test Ea, Unpackaged Shock)

Emissions

Group 1, Class A
CISPR 11

ESD Immunity

8kV air discharges
IEC 61000-4-2

Radiated RF Immunity 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz
IEC 61000-4-3

EFT/B Immunity

+1kV @ 5kHz on power ports
+2kV @ 5kHz on signal ports
+2kV @ 5kHz on communications ports
IEC 61000-4-4

Surge Transient
Immunity

+1kV line-line(DM) and +2kV line-earth(CM) on power ports
+1kV line-line(DM) and +2kV line-earth(CM) on signal ports
+2kV line-earth(CM) on shielded ports
IEC 61000-4-5

Conducted RF
Immunity

10Vrms with 1kHz sine-wave 80%AM from 150kHzto 80MHz
IEC 61000-4-6

Enclosure Type Rating None (open style)

Mounting

DIN rail or screw

Dimensions

52x118.5x42mm (2.03x4.62x1.64in)

Weight

0.3lb (0.1kg)