Channel configuration – Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual
Page 108
Advertising
Publication 1746-UM008B-EN-P - December 2006
108 Application Examples
Channel Configuration
Configure the RTD channel with the following setup:
• 200 Ω Platinum RTD
• °F in whole degrees
• Zero data word in the event of an open or short circuit
• 10 Hz input filter
• 2.0 mA excitation current
Channel Configuration Worksheet (With Settings Established for Channel 0)
Input Type Select
Data Format select
Broken Input Select
Temperature Units Select
Filter Frequency Select
Channel Enable
Excitation Current Select
Scaling Select
Not Used
Channel 0
Channel 1
Channel 2
Channel 3
11
12
13
14
15
0
9
10
8
6
7
4
5
0 1
2
3
0
0
0
Bit Number
0
0
0
1
0
0
1
0
0
0
1
0
0
0
1