42 Install and Wire the Module
• Tighten terminal screws using a flat or cross-head screwdriver.
Each screw should be turned tight enough to immobilize the
wire’s end. Excessive tightening can strip the terminal screw.
The torque applied to each screw should not exceed 0.565 Nm
(5 in-lb) for each terminal.
• Follow system grounding and wiring guidelines found in your
SLC 500 Installation and Operation Manual, publication
1747-UM011.
RTD Connections to Terminal Block
Chl 1
Shield
Shield
Chl 0
RT D
Shield
RT D
Chl 0
Sense
Chl 1
Sense
Chl 0
Return Chl 1
Return
Shield
Chl 3
Chl 2
RT D
RT D
Chl 2
Sense Chl 3
Sense
Chl 2
Return
Chl 3
Return
Shield
Shield
Cable Shield
Cable Shield
Cable Shield
Add Jumper
RTD
Return
RTD
Return
Shield
Ch 0 RTD
Ch 0 Sense
Ch 0 Return
Return
RTD
Return
RTD
Shield
Ch 0 RTD
Ch 0 Sense
Ch 0 Return
Return
Sense
Sense
RTD
Return
RTD
Shield
Ch 0 RTD
Ch 0 Sense
Ch 0 Return
Return
Sense
Sense
Two-wire RTD Interconnection
Four-wire RTD Interconnection
Three-wire RTD Interconnection
Belden #9501 Shielded Cable
Belden #83503 or Belden #9533 Shielded Cable
Belden #83503 or Belden #9533 Shielded Cable
Leave one sensor wire open
Terminal Pin-outs
RTD