Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual
Page 129

Publication 1746-UM008B-EN-P - December 2006
Configuration Worksheet for RTD/Resistance Module 129
Bits 9
and 10
Filter Frequency
Select
00 = 10 Hz
01 = 50 Hz
10 = 60 Hz
11 = 250 Hz
Bit 11
Channel Enable
0 = channel disabled
1 = channel enabled
Bit 12
Excitation Current
Select
0 = 0.2 mA
1 = 0.5 mA
Bit 13
and 14
Scaling Select
00 = module defined
scaling (default)
01 = config. words 4 & 5 for
scaling
10 = config. words 6 &
7 for scaling
11 = Not used
(config error)
Bit 15
Not Used
0 = always make this setting
(1)
Actual value at 0 °C (32 °F) is 9.04
Ω per SAMA standard RC21-4-1966.
(2)
Actual value at 0 °C (32 °F) is 100
Ω per DIN standard.
(3)
Values are expressed in 0.1 degree/step or 0.1
Ω/step (applies to all pots, except 150 Ω type). For the 150 Ω pot input type, the values are expressed in 0.01 Ω/step.
(4)
Values are expressed in 1 degree/step or 1
Ω/step (applies to all pot, except 150 Ω type). For the 150 Ω pot input type, the values are expressed in 0.1 Ω/step.