I/o memory mapping, Input data file, Configuration file – Rockwell Automation 1769-IQ32T Compact Module User Manual

Page 15

Advertising
background image

Compact 32-point 24V dc Sink/Source Input Module 15

Publication 1769-IN072A-EN-P - June 2005

I/O Memory Mapping

Input Data File

For each input module, slot x, words 0-1 in the input data file contain the current state of the
field input points.

r=read

Configuration File

For each input module, slot x, words 0-1 in the configuration file controls the amount of
filtering applied to the signals from the field input points. The amount of filtering applied can
be configured individually for both the On-to-Off and Off-to-On edges of each isolated
group

(1)

of input signals.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

1

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r

(1)

See Input Specifications on page 17 for isolated group input assignments.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Filter configuration

group 2 On-to-Off

Filter configuration

group 2 Off-to-On

Filter configuration

group 1 On-to-Off

Filter configuration

group 1 Off-to-On

1

Filter configuration

group 4 On-to-Off

Filter configuration

group 4 Off-to-On

Filter configuration

group 3 On-to-Off

Filter configuration

group 3 Off-to-On

OFF_Filter or ON_Filter (Binary)

Filter Time

0000 (default)

8.0 ms

0001

4.0 ms

0010

2.0 ms

0011

1.0 ms

0100

0.5 ms

0101

0.1 ms

0110

0.0 ms

0111…1111

Not used