Spare/replacement module parts, Specifications, General specifications – Rockwell Automation 1769-IQ32T Compact Module User Manual

Page 16

Advertising
background image

16 Compact 32-point 24V dc Sink/Source Input Module

Publication 1769-IN072A-EN-P - June 2005

Spare/Replacement Module Parts

• 1746-N3: Connector kit (1 connector, 40 terminals per kit)

Specifications

General Specifications

Specification

Value

Dimensions

118 mm (height) x 87 mm (depth) x 35mm (width)

height including mounting tabs is 138 mm

4.65 in (height) x 3.43 in (depth) x 1.38 in (width)

height including mounting tabs is 5.43 in

Approximate Shipping Weight

(with carton)

230 g (0.51 lbs)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 inches maximum
peak-to-peak

Shock

Operating: 30G panel mounted (20G DIN rail mounted)

Non-Operating: 40G panel mounted (30G DIN rail mounted)

Agency Certification

• C-UL certified (under CSA C22.2 No. 142)

• UL 508 listed

• CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

(UL 1604, C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity (IEC1000-4-2)

4kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15 to 80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.