Input specifications – Rockwell Automation 1769-IQ32T Compact Module User Manual

Page 17

Advertising
background image

Compact 32-point 24V dc Sink/Source Input Module 17

Publication 1769-IN072A-EN-P - June 2005

Input Specifications

Specification

1769-IQ32T

Voltage Category

24V dc (sink/source

(1)

)

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and
sourcing output module circuits are the commonly used options.

Operating Voltage Range

20.4 to 26.4V dc at 60°C (140°F)

Number of Inputs

32

Bus Current Draw (max.)

170 mA at 5V dc (0.85 W)

Heat Dissipation

4.77 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.)

Digital Filter

OFF to ON: 0 s, 100 µs, 500 µs, 1 ms, 2 ms, 4 ms, 8 ms

ON to OFF: 0 s, 100 µs, 500 µs, 1 ms, 2 ms, 4 ms, 8 ms

Hardware Delay

On Delay: 0.1 ms (typical), 0.42 ms (max)

Off Delay: 0.25 ms (typical), 1.0 ms (max)

Off-State Voltage (max.)

11V dc

Off-State Current (max.)

1.7 mA

On-State Voltage (min.)

19V dc

On-State Current (min.)

3.0 mA

Inrush Current (max.)

5 mA

Nominal Impedance

5.6 kohm

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from the power
supply or controller.)

Input Point to Bus (Compact Bus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

Group 1: inputs 0 to 7

Group 2: inputs 8 to 15

Group 3: inputs 16 to 23

Group 4: inputs 24 to 31

Isolated groups operate in either sink or source configurations.

Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

76

Advertising