3-16 ProcessLinx TagMap Configuration

By default, ProcessLinx attempts to use the item file when browsing
ProcessLogix tags used to map tags. If this file does not exist then each time
the “Add TagMap(s)” function is executed it parses and compiles all exported
function block files and creates the function block list with no connectable
items to map to. If this happens, create a ProcessLinx.itm file manually by
performing the following steps:

1. Run Control Builder and export the desired blocks using the File

Export function from the main menu in ControlBuilder.

2. Stop and exit ProcessLinx.

3. Run the Registry Editor program <Reedited> from the Start

Run

dialog box.

4. Create and set the following keys to specified values under the branch:

<HKEY_LOCAL_MACHINE\SOFTWARE\RockwellSoftware\PrcessLinx\Options>

5. Start ProcessLinx and select Add Tag Map(s).

ProcessLinx creates the specified item file to browse available points if
you have defined the HWHsc.OPCServer for the server.

6. Stop and exit ProcessLinx.

7. Delete only the 2 created registry keys above. Do not delete the

<DefaultBrowseFile> registry entry. If these 2 keys are not deleted, the
item file will be created each time the Add Tag Map(s) function is exe-
cuted.

8. Start ProcessLinx again.

9. Execute the Add Tag Map(s) function and the available items appear

WARNING

!

Rockwell Automation holds no responsibility for damages
to property and personnel or loss of time that may occur
when making changes to the Registry.

Table 3.D Registry Key

Registry Key to create

Key Type

Set the value of this key to:

ExportBrowseFileName

STRING

C:\Program Files\ProcessLogix\ProcessLinx.itm

or set the path to the location of
ProcessLinx.exe. This setting should match
the <DefaultBrowseFile> string value.

ExportBrowseFile

DWORD

1