Server status, Server status -4 – Rockwell Automation 1757-PROCESSLINX ProcessLinx OPC Server to Server Software User Manual User Manual

Page 48

Advertising
background image

Publication 1757-UM002B-EN-P - January 2003

4-4 ProcessLinx Runtime Operation

Server Status

You can view the runtime status of each Pipe’s OPC Servers. Select Utility

⇒

Server Status…. Or right mouse click on a Pipe or Group and click Server
Status
.

Figure 4.2 Server Status Dialog Box

A switchover to the redundant OPC Server can be forced by clicking Switch
Server
. If a redundant Server is not defined, ProcessLinx disconnects from the
primary Server and then reconnects to it. If a redundant Server is defined,
ProcessLinx attempts a connection to it. ProcessLinx attempts the connection
for the “Number of Retries” specified in the Utility

⇒

Configure Options

menu. After the number of retries has been exceeded, ProcessLinx then
attempts to fail over to the first Server. This connection attempt / fail over
process continues until a successful connection has been established. Messages
for each failed attempt are logged to the ProcessLinx message pane and error
log.

Advertising