Server Status
You can view the runtime status of each Pipe’s OPC Servers. Select Utility
⇒
Server Status…. Or right mouse click on a Pipe or Group and click Server
Status.
Figure 4.2 Server Status Dialog Box
A switchover to the redundant OPC Server can be forced by clicking Switch
Server. If a redundant Server is not defined, ProcessLinx disconnects from the
primary Server and then reconnects to it. If a redundant Server is defined,
ProcessLinx attempts a connection to it. ProcessLinx attempts the connection
for the “Number of Retries” specified in the Utility
⇒
Configure Options
menu. After the number of retries has been exceeded, ProcessLinx then
attempts to fail over to the first Server. This connection attempt / fail over
process continues until a successful connection has been established. Messages
for each failed attempt are logged to the ProcessLinx message pane and error
log.