34 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
22.
Click Next.
If an RSNetWorx for DeviceNet configuration file (filename *.dnt)
already exists for the linking device, enter or browse to the appropriate
filename. Doing so allows RSNetWorx for DeviceNet to launch directly
from RSLogix 5000 software.
23.
Click Finish.
You can now use the linking device as both a bridge and a scanner.
RSLogix 5000 Software Error Codes
This Error code
Means
So you should
16#0203
Connection timed out
Check IP configuration and Ethernet cabling
16#0204
Connection Request Error: Connect
request timed out
Check IP configuration and Ethernet cabling
16#0103
Service Request Error: CIP transport
class not supported
Check for valid RPI range (for example,
2…3200ms)
16#0005
Connection Request Error: Bad class.
Check for correct assembly instance numbers
in connection parameters