Devicenet network status indicator – Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual
Page 42

42 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
DeviceNet Network Status Indicator
I/O Status Indicator States
Indicator
Status
Description
Flashing green
Idle
Module is in Idle mode.
Solid green
Running
Module is in Run mode.
Solid orange
Hardware Initialization
The status indicator will be in this state immediately
after power is applied.
Flashing red/green
Error
A fault has been detected.
Off
No I/O
No DeviceNet I/O configured.
DeviceNet Network Status Indicator States
Indicator
Status
Description
Solid green
Online and
communicating
The linking device is on the DeviceNet network and
communicating with at least one device.
Flashing green
Online, no
communication
The linking device is on the DeviceNet network and
is not currently communicating with any devices.
Solid red
DeviceNet interface
fault
A major fault in the DeviceNet interface has been
detected. Possible causes include Bus-off or
duplicate MAC ID.
Flashing red
Connection time-out
A connection with at least one slave device has
timed out.