Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual
Page 53

Ethernet-to-DeviceNet Linking Device 53
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Relative humidity
• IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
• IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating
• IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
• IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
ESD immunity
• IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
• IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
1890 MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B immunity
• IEC 61000-4-4
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
Surge transient immunity
• IEC 61000-4-5
±1 kV line-line(DM) and ±2 kV
line-earth(CM) on power ports
±2 kV line-earth(CM) on communication
ports
Conducted RF immunity
• IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
Environmental Specifications - 1788-EN2DN
Attribute
1788-EN2DN