12 ArmorBlock MaXum 16 Sinking Output Module Series B

Publication 1792D-IN041B-EN-P - September 2000

Specifications

16 Output Module - Cat. No. 1792D-OVT16E

Max.

Min.

Outputs per block

16 sinking outputs labeled 00 through 15

Output Auxiliary Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.3A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

4.0A

-

Surge Current - for 10 ms,
repeatable every 2s

0.6A

-

Indicators

Net/Mod Status - red/green
Auxiliary Power - green
Logic Status - red/green
Point LED - yellow/orange/red

Communication Rate

•125Kbps @ 500 meters (1600 feet) for thick cable,

flat media length 375 meters (1230 feet)

•250Kbps @ 200 meters (600 feet) for thick cable,

flat media length 150 meters (492 feet)

•500Kbps @ 100 meters (330 feet) for thick cable,

flat media length 75 meters (246 feet)

DeviceNet Power:

Voltage
Current

25V dc max
125mA

11V dc min
250mA

Auxiliary Power:

Voltage
Current

30V dc
4A

10V dc
4A

Dimensions (assembled to base)
inches - (millimeters)

1.9H x 2.7W x 6.85D
(48.26)H x (68.6)W x (174)D

Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating

Non-operating

Vibration

-25 to 60

o

C (-13 to 140

°

F)

-25 to 80

o

C (-13 to 176

°

F)

Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11 (+1) ms pulse width
Tested 10g @ 10-500 Hz per IEC 68-2-6

Conductors

Publication DN-6.7.2