Connect the output cord sets to the maxum module – Rockwell Automation 1792D-OVT16E ArmorBlock MaXum 16 Sinking Output Module, Series B User Manual
Page 6

6 ArmorBlock MaXum 16 Sinking Output Module Series B
Publication 1792D-IN041B-EN-P - September 2000
Connect the Output Cord Sets to the MaXum Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Eight micro caps cover the connectors on your module. Remove the
caps and connect your cord sets to the appropriate ports. This
product has two outputs per connector. Use a “Y” splitter cable for
access to all output connections.
Use the micro caps to cover and seal unused ports. A pinout diagram
for the connectors is shown below.
Please refer to publication 889-5.0 for Rockwell Automation cables
and cord sets offerings.
ATTENTION
!
• Make sure all connectors and caps are securely
tightened to properly seal the connections
against leaks and maintain IP67 requirements.
• For maximum noise immunity, output cable
return wires must be properly terminated.
When outputs are connected in loopback,
return wires should be connected together.
• I/O cable length should be less than 30 meters.
1
5
3
4
2
Micro-Connector
(View into Sockets)
Pin 1 Auxiliary +24V dc
Pin 2 Output B
Pin 3 Not used
Pin 4 Output A
Pin 5 Not Used
41452