8 ArmorBlock MaXum 16 Sinking Output Module Series B

Publication 1792D-IN041B-EN-P - September 2000

Communicate with Your ArmorBlock MaXum I/O
Module

This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.

The module consumes and produces output data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. This 16 output module consumes the
message, updates outputs, and produces a response. The response
has output data, output faults, and contains the status of the Auxiliary
power.

Change-of-State - productions occur when an output changes or a
fault condition occurs. If no output or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate. Consumption occurs when data
changes and the master produces new output data to the I/O block.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

2 Bytes

1 Byte

Polled

2 Bytes

1 Byte

Change-of-State

2 Bytes

1 Byte

Bit

07

06

05

04

03

02

01

00

Produces 0

RSVD

OPWR

RSVD

RSVD

RSVD

RSVD

RSVD

RSVD

Consumes 0

O7

O6

O5

O4

O3

O2

O1

O0

Consumes 1

O15

O14

O13

O12

O11

O10

O9

O8

Where: RSVD = Reserved OPWR = Output Power (Auxiliary Power) O = Output