10 GuardLogix Controllers

Publication 1756-IN045E-EN-P - October 2009

Check the BAT Status Indicator

Follow these steps for both the 1756-L6

xS controller and 1756-LSP safety partner.

1. Turn on the chassis power.

2. Check the status of the BAT indicator.

3. Check that the battery is correctly

connected to the controller or safety
partner.

4. If the BAT status indicator remains on, install another battery.

5. If the BAT status indicator remains on after you complete step 4, contact

your Rockwell Automation representative or local distributor.

Check the OK Status Indicator

Follow these directions for both the 1756-L6

xS controller

and 1756-LSP safety partner.

If

Then

Off

Go to Update the Controller on page 11.

On

Go to step 3.

If the OK
Indicator
is

Then

Next step

Solid
green

The controller is OK and its
firmware has been updated.

No further action is required.

Flashing
red

The controller is OK but it
requires a firmware update.

Go to Update the Controller
below.

BAT Status

Indicator

OK
Status
Indicator