Environmental specifications – Rockwell Automation 1756-LSP GuardLogix Controller User Manual

Page 17

Advertising
background image

GuardLogix Controllers 17

Publication 1756-IN045E-EN-P - October 2009

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60 °C (32…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

-40…85 ° C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Un-packaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz

Operating shock

IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Nonoperating shock

IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 MHz 50% Pulse 100% AM @ 1890 MHz

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV @ 5 kHz on communication ports

Surge transient
immunity

IEC 61000-4-5:

±2 kV line-earth (CM) on communication ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)