Connect the Battery

This controller contains a lithium battery, which is intended to be replaced during
the life of the product.

To maintain the memory of the controller while the controller is without power,
connect a battery. Follow the procedure for both the 1756-L6

xS controller and

1756-LSP safety partner.

Follow these steps to install a new 1756-BA2
battery:

1. Insert the battery as shown.

2. Connect the battery:

+ Red

- Black

3. Write the date you installed the battery

on the battery label and attach the
label to the inside of the controller
door.

WARNING

When you connect or disconnect the battery, an electrical arc can occur. This
could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

For safety information on the handling of lithium batteries, including handling
and disposal of leaking batteries, see Guidelines for Handling Lithium
Batteries, publication

AG 5-4

.

ATTENTION

Store batteries in a cool, dry environment. We recommend 25 °C (77 °F) with
40%…60% relative humidity. You may store batteries for up to 30 days
between -45…85 °C (-49…185 °F), such as during transportation. To avoid
possible leakage, do not store batteries above 60 °C (140 °F) for more than
30 days.

IMPORTANT

Connect only a 1756-BA2 battery to the controller. If you connect a different
battery, you may damage the controller.