Choose the Operating Mode of the Controller

Replace the Battery

IMPORTANT

Controller communication occurs regardless of mode.

All modes produce and consume tags.

ATTENTION

To prevent possible battery leakage, even if the BAT LED is off, replace a
1756-BA2 battery according to the following schedule.

No

Do you want to prevent
RSLogix 5000 software
from changing the mode?

Do you want to
execute the logic
in the controller?

Do you want the logic
to control the output
devices?

Turn the keyswitch to PROG
and then to REM
(Remote Program mode).

Turn the keyswitch to
PROG (Program mode).

Turn the keyswitch to RUN
and then to REM
(Remote Run mode).

No

Yes

Do you want to prevent
RSLogix 5000 software from:

changing the mode?

downloading a project?

performing online edits?

Turn the keyswitch to RUN
(Run mode).

No

Yes

Do you need to schedule
a network?

No

Yes

Outputs revert to their configured state for Program mode.

A

This includes Message (MSG) instructions.

B

No

1. Turn the keyswitch to REM.
2. Go online with RSLogix 5000

software and choose Test
mode.

Yes

B

A

A

A

Yes

If the temperature 2.54 cm (1
in.) below the chassis is

Replace the battery within

0…35 °C (32 °…95 °F)

No replacement is required until the BAT LED turns on

36…40 °C (96 °…104 °F)

3 years

41…45 °C (105 °…113 °F)

2 years

46…50 °C (114 °…122 °F)

16 months

51…55 °C (123 °…131 °F)

11 months

56…60 °C (132 °…140 °F)

8 months