Wiring mixed transmitter types, Labeling the terminals – Rockwell Automation 1769-IF4 Compact (Series B or Later) Analog Input Module User Manual

Page 13

Advertising
background image

Compact™ 1769-IF4 (Series B or Later) Analog Input Module 13

Publication 1769-IN048A-EN-P

Wiring Mixed Transmitter Types

(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA

minimum.

(2) Series B and later modules provide this option.

Labeling the Terminals

A removable, write-on label is provided with the module. Remove the label
from the door, mark the identification of each terminal with permanent ink,
and slide the label back into the door. Your markings (ID tag) will be
visible when the module door is closed.

+

V in 0 +

V/I in 0 -

I in 0 +

ANLG Com

V in 1 +

V/I in 1 -

I in 1 +

ANLG Com

V in 2 +

V/I in 2 -

I in 2 +

ANLG Com

V in 3 +

V/I in 3 -

I in 3 +

ANLG Com

+24V dc

dc NEUT

+

+

+

+

+

+

+

Single-ended

Voltage

Transmitter

Differential

Voltage

Transmitter

Differential

Current

Transmitter

2-Wire

Current

Transmitter

Signal

Signal

Signal

Signal

Supply

Supply

1769-IF4 Terminal Block

Sensor/

Transmitter

Supply

External 24V dc
Power Supply

(1)

(optional)

(2)