Compact™ 1769-IF4 (Series B or Later) Analog Input Module 17

Publication 1769-IN048A-EN-P

Specifications

General Specifications

Specification

Value

Dimensions

118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm

4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.

Approximate Shipping Weight
(with carton)

300g (0.65 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak

Relay Operation: 2G

Shock

Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)

Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)

Non-Operating: 40G panel mounted
(30G DIN rail mounted)

Agency Certification

• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

• ESD Immunity (IEC1000-4-2)

• 4 kV contact, 8 kV air, 4 kV indirect

• Radiated Immunity (IEC1000-4-3)

• 10 V/m , 80 to 1000 MHz, 80% amplitude modulation,

+900 MHz keyed carrier

• Fast Transient Burst (IEC1000-4-4) • 2 kV, 5kHz

• Surge Immunity (IEC1000-4-5)

• 1 kV galvanic gun

• Conducted Immunity (IEC1000-4-6) • 10 V, 0.15 to 80MHz

(1)

(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is

30 MHz to 1000 MHz.