I/o memory mapping, Wire size and terminal screw torque, Input data file – Rockwell Automation 1769-IF4 Compact (Series B or Later) Analog Input Module User Manual

Page 15

Advertising
background image

Compact™ 1769-IF4 (Series B or Later) Analog Input Module 15

Publication 1769-IN048A-EN-P

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

I/O Memory Mapping

Input Data File

For each input module, slot x, words 0-3 in the input data file contain the
analog values of the inputs.

The bits are defined as follows:

• SGN = Sign bit in two’s complement format

• Sx = General status bit for channels 0 through 3. This bit is set (1) when

an error (over- or under-range) exists for that channel.

• Ux = Under-range flag bits for channels 0 through 3. These bits can be

used in the control program for error detection.

• Ox = Over-range flag bits for channels 0 through 3. These bits can be

used in the control program for error detection.

Wire Type

Wire Size

Terminal Screw

Torque

Retaining Screw

Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Input Data Channel 0

1

SGN

Analog Input Data Channel 1

2

SGN

Analog Input Data Channel 2

3

SGN

Analog Input Data Channel 3

4

Not Used

S3

S2

S1

S0

5

U0

O0

U1

01

U2

O2

U3

O3

Set to 0