16 Compact™ 1769-IF4 (Series B or Later) Analog Input Module

Publication 1769-IN048A-EN-P

Configuration Data File

The manipulation of the bits from this file is normally done with
programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.)
during initial configuration of the system. In that case, graphical screens are
provided by the programmer to simplify configuration. However, some
systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be
altered as part of the control program, using communication rungs. In that
case, it is necessary to understand the bit arrangement. Refer to the
Compact™ Analog I/O User Manual, publication number
1769-UM002A-EN-P for additional details.

Words 0 to 3 of the configuration file allow you to change the parameters
of each channel independently. For example, word 0 corresponds to
channel 0.

Define

To Select

Make these bit settings

15

14

13

12

11

10

9

8

4-7

3

2

1

0

Input Filter
Selection/
-3 dB
Frequency

60 Hz/15.7 Hz

Not

Us

ed

0

0

0

0

50 Hz/13.1 Hz

0

0

0

1

Not Used

0

0

1

0

250 Hz/65.5 Hz

0

0

1

1

500 Hz/131Hz

0

1

0

0

Spare

(1)

(1) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module

configuration error.

Input Type/
Range

-10 to +10V dc

0

0

0

0

0 to 5V dc

0

0

0

1

0 to 10V dc

0

0

1

0

4 to 20 mA

0

0

1

1

1 to 5V dc

0

1

0

0

0 to 20 mA

0

1

0

1

Spare

(1)

Input Data
Format

Raw/Proportional
Data

0

0

0

Engineering Units

0

0

1

Scaled-for-PID

0

1

0

Percent Range

0

1

1

Spare

(1)

Enable
Channel

Enabled

1

Disabled

0