5–2

Install and Connect Remote I/O Scanner and Adapter

Publication 1772Ć10.1 - March 1996

Install and Connect Remote I/O Adapter

a

Set the module switches.

b

Set the module configuration plugs.

Position all 3 jumpers

on the left 2 pins

10797ĆI

1 2 3 4 5 6 7 8

O

N
O

F

F

O

N
O

F

F

1 2 3 4

First I/O group number

I/O rack number

Address Switch Assembly

(S1)

Switch Assembly

(S2)

SD Ć always OFF

SD2 Ć without complementary I/O Ć always OFF

SD2 Ć with complementary I/O Ć

ON Ć Primary chassis

OFF Ć Complementary chassis

Pressed in at top

Closed (ON)

Pressed in at bottom

Open (OFF)

Maximum I/O

chassis distance

SD Ć always ON

SD2 Ć without complementary I/O

Ć always ON
SD2 Ć with complementary I/O Ć

ON Ć Primary chassis

OFF Ć Complementary chassis

Always ON

5 6

Link Response Ć ON for series B emulation

Scan Ć on for all but last 4 slots

off for all slots

OFF for unrestricted

Switch Position

1 2

57.6K Baud Ć 10,000ft

115.2K Baud Ć 5,000ft

Not Used

Not Used

10798ĆI

ATTENTION: Link response switch must

be ON when using the following scanner

modules: 1772ĆSD2

ON

OFF

OFF

OFF

ON

ON

ON

OFF

Off