1772-10.1, 1 - configure and ground i/o chassis, Step, Configure and ground i/o chassis – Rockwell Automation 1772-LPx DATA PLC-2 FAMILY PROG CONTRL User Manual

Page 6: Configure i/o chassis

Advertising
background image

Step

1

Publication 1772Ć10.1 - March 1996

Configure and Ground I/O

Chassis

Configure I/O Chassis

If you are using a power supply outside of the rack, plug the 9Ćpin connector of the power cable

into the 9Ćpin socket on the I/O chassis backplane and leave the other end of the power cable

loose. (Later, you will connect this end of the cable to the power supply.)

Set the backplane switches.

a

b

Switch

Group

Assembly

10183ĆI

Input

Power

Socket

Rack:

Switch:

1

2

3

1
2
3
4
5
6
7

on

off

on
on
on

on
on

on
on

on

on

on

on

off
off

off
off

off

off

off

off

Processor Restart Lockout - 2

When ON, processor can restart I/O chassis

When OFF, I/O chassis must be restarted at the chassis.

Addressing Switch Ć- 5

ON Ć 1Ćslot addressing selected

OFF Ć 2Ćslot addressing selected

Last State Switch Ć

When ON, outputs of this chassis remain in last

state when a fault is detected.

When OFF, outputs of this I/O chassis are

deenergized when a fault is detected.

Always OFF

Last Chassis Switch Ć- 8

ON Ć Chassis does not contain the highest numbered I/O group

for the associated rack number

OFF Ć Chassis does contain the highest numbered I/O group for

the associated rack number

If you have only a primary chassis, set this

switch to OFF.

If you have both primary and complementary

chassis, set the primary chassis to ON and the

complementary chassis to OFF.

10802ĆI

ATTENTION: Set switch 1 to the OFF position

to deenergize outputs wired to this chassis when a fault is

detected. If switch 1 is set to the ON position, outputs connected

to this chassis remain in their last state when a fault occurs and

machine motion may continue after fault detection.

O

O

1
2
345

6
7
8

N

F

F

Always OFF

Local I/O

Remote I/O