1–2

Configure and Ground I/O Chassis

Publication 1772Ć10.1 - March 1996

Install keying bands.

See the appropriate product data for the module

you are installing to determine the proper keying

positions for each module.

c

24

68

10

12

14

16

18

20

22

24

26

28

30

32

34

36

Keying

Bands

Backplane

Socket

10170-I

Set the power supply configuration plug.

d

USING

POWER

SUPPLY

MODULE IN

THIS

CHASSIS?

I/O Chassis

Power Supply

Configuration

Plug

YN

Y

N

N

Y

Set this plug to the left (Y) position if you

use a slot power supply module.

Set this plug to the right (N) position if you

use an external supply.

Ground I/O Chassis

Ground Bus

Enclosure

Grounding Electrode

Conductor

To

Earth

Ground

Processor

PLCĆ2/30

When using this grounding configuration, make no connections to EQUIP GND

on the power supply terminal strips. This can cause ground loops.

Ground Lug

Ground Lug

Star

Washer

Nut and

Captive Washer

I/O Chassis Wall