Specifications – Rockwell Automation 1792D-12BVT4D ArmorBlock MaXum 12 Input/4 Output Module Series B User Manual

Page 12

Advertising
background image

12 ArmorBlock MaXum 12 Input/ 4 Output Module Series B

Publication 1792D-IN004B-EN-P - August 2000

Specifications

12 Input / 4 Output Module - Cat. No. 1792D-12BVT4D

Input Specifications

Max.

Min.

Inputs per block

12 - 3 wire or dry contact PNP or NPN devices or 6 -
4 wire PNP or NPN devices

Sensor Source Current (per input)

See the graph below.

Off-Wire Sense Current

0.5mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Output Specifications

Max.

Min.

Outputs per block 4 sourcing outputs labeled O0 through O3

Off Peak Blocking Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

2.0A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

4.0A

-

Surge Current - for 10ms,
repeatable every 2s

4.0A

-

No Load Sense Current (On-state)

0.18A

-

General Specifications

Indicators

Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red

Communication Rate

125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)

DeviceNet Power

Voltage
Current

Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.

25V dc max
175mA max (no sensors)

11V dc min
up to 1.6A (12
sensors @ 50mA per
sensor)

Auxiliary Power

Voltage

Current

30V dc max
4A max

10V dc min
4A max

Dimensions (assembled to base)
inches - (Millimeters)

1.9H x 2.7W x 6.85D
(48.26)H x (68.6)W x (174)D (millimeters)

Advertising