Rockwell Automation 1792D-12BVT4D ArmorBlock MaXum 12 Input/4 Output Module Series B User Manual

Page 6

Advertising
background image

6 ArmorBlock MaXum 12 Input/ 4 Output Module Series B

Publication 1792D-IN004B-EN-P - August 2000

Use the micro caps to cover and seal unused ports. Pinout diagrams
for the connectors are shown next.

Molded I/O cables with LEDs embedded in the connector are
incompatible with MaXum universal sink/source inputs. Please refer
to publication 889-5.0 for Rockwell Automation cables and cord sets

offerings.

IMPORTANT

If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.

ATTENTION

!

• Make sure all connectors and caps are

securely tightened to properly seal the
connections against leaks and maintain
IP67 requirements.

• For maximum noise immunity, input and

output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.

• I/O cable length should be less than 30

meters.

Input Micro-Connector
(View into Socket)

Pin 1 Sensor Source voltage
Pin 2 Input B

Pin 3 Return Logic Ground

1

Pin 4 Input A
Pin 5 Not Used

Output Micro-Connector
(View into Socket)

Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used

41452

1

Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.

Advertising