Rockwell Automation 1792D-12BVT4D ArmorBlock MaXum 12 Input/4 Output Module Series B User Manual

Page 5

Advertising
background image

ArmorBlock MaXum 12 Input/ 4 Output Module Series B 5

Publication 1792D-IN004B-EN-P - August 2000

To install the module:

1. Position the module over the mounted cable base. Align the

three captive screws in the module with the accepting
receptacles in the base.

2. Tighten the screws with a torque of 8 inch-pounds to secure

the module to the base.

Note: Dimensions change according to the cable base and module

combination used.

Connect the Input / Output Cord Sets to the MaXum
Module

This module uses 5 pin micro (12mm) style PCB mounted connectors.

Eight micro caps cover the connectors on your module. Remove the
caps and connect your cord sets to the appropriate ports. This
product has two inputs or outputs per I/O connector. Use a “Y”
splitter cable for access to all I/O connections.

IMPORTANT

Proper alignment of the screws is necessary to
complete the connections between the module
contacts and the cable contacts.

Align the
screws to
properly
assemble the
module to the
base.

Cable Base
1792D-CBFM is used for
this example.

Assembled
dimensions
in (mm)

1.9 (48.26)

2.7 (68.6)

6.85 (174)

41522

Advertising