Specifications

Specification:

Value:

Module Location

Any slot in the ControlLogix chassis

Maximum Backplane
Current Load

700mA @ 5.1V DC

3mA @ 24V DC from I/O chassis backplane

Power Dissipation

3.65W maximum

Isolation voltage
(continuous-voltage
withstand rating)

50V

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock),

0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):

5 to 95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2g @ 10-500Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30g

Non-Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50g

Emissions

CISPR 11:

Group 1, Class A