28 EtherNet/IP Web Server Module

Publication

1756-IN588A-EN-P - February 2004

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to
1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on communications ports

Surge Transient Immunity

±2kV line-earth(CM) on shielded ports

±2kV line-earth unshielded ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Conductors - Wiring
Category

2

1

- on communications ports

EtherNet/IP Connector

RJ45 Category 5

Specification:

Value:

Advertising