Publication 1738-IN021A-EN-E - January 2007

ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics 11

Specifications

Following are specifications for the ArmorPoint 24V dc 4-channel Digital
Input Module.

ArmorPoint 24V dc 4-channel Digital Input Module

General Specifications

Inputs

4 (1 group of 4) nonisolated, sinking

Voltage, Off-State Input, Maximum

5V dc

Voltage, On-State Input

Maximum
Minimum
Nominal

28.8V dc
11V dc
24V dc

Current, Off-State Input, Maximum

1.5 mA

Current, On-State Input

Maximum
Minimum
Nominal

15 mA

2 mA

3 mA @ 24V dc

Input Delay Time OFF to ON

0-65535 us selectable

(3)

in 1 us intervals (rounded to nearest 333 us)

Default is 1000 us.

Input Delay Time, ON to OFF

0-65535 us selectable

(4)

in 1 us intervals (rounded to nearest 333 us)

Default is 1000 us.

Field Power Bus Supply

Voltage Range
Nominal


10-28.8V dc

24V dc

Keyswitch Position

1

Reverse Polarity Protection

Yes

LED Indicators

1 green/red network status, logic side

1 green/red module status, logic side

4 yellow/red input status, logic side

PointBus Current, Maximum

50 mA @ 5V dc

Power Dissipation, Maximum

0.6W max @ 28.8V dc

Thermal Dissipation, Maximum

1.9BTU/hr max @ 28.8V dc

Isolation Voltage

(continuous-voltage withstand rating)

50V (continuous), Reinforced Insulation Type

Tested at 1000V dc for 60s, field-side to system

Dimensions

Imperial

Metric

4.72H x 2.83W x 1.65D (Includes I/O module and mounting base)

120H x 72W x 42D (Includes I/O module and mounting base)

Enclosure Type Rating

Meets IP65/66/67/69k (when marked)

Mounting Base Screw Torque

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Weight

Imperial

Metric


0.64 lb.

0.29 kg

Wiring Category

(1)

1 - on signal ports