Rockwell Automation 1738-IB4DM12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics I.I. User Manual

Page 8

Advertising
background image

Publication 1738-IN021A-EN-E - January 2007

8 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics

Data Map - Produced Assembly Instance 23

Default Data Map - Configuration Assembly Instance 103

Message Size: 1 Bytes

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault
3

Fault
2

Fault
1

Fault
0

Input
3

Input
2

Input
1

Input
0

Consume (Tx)

No consumed data

Where: Fault = open wire or short circuit.

Message Size: 18 Bytes

7

6

5

4

3

2

1

0

Consume 0

Input 0 Off to On Filter Byte 0

Consume 1

Input 0 Off to On Filter Byte 1

Consume 2

Input 0 On to Off Filter Byte 0

Consume 3

Input 0 On to Off Filter Byte 1

Consume 4

Input 1 Off to On Filter Byte 0

Consume 5

Input 1 Off to On Filter Byte 1

Consume 6

Input 1 On to Off Filter Byte 0

Consume 7

Input 1 On to Off Filter Byte 1

Consume 8

Input 2 Off to On Filter Byte 0

Consume 9

Input 2 Off to On Filter Byte 1

Consume 10

Input 2 On to Off Filter Byte 0

Consume 11

Input 2 On to Off Filter Byte 1

Consume 12

Input 3 Off to On Filter Byte 0

Consume 13

Input 3 Off to On Filter Byte 1

Consume 14

Input 3 On to Off Filter Byte 0

Consume 15

Input 3 On to Off Filter Byte 1

Consume 16

Autobaud
Disabled

Enable
OW3

Enable
OW3

Enable
OW3

Enable
OW3

Consume 17

Produced Assembly Instance

Produce (Tx)

No produced data

Where: OW = open wire.