Rockwell Automation 1738-IB4DM12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics I.I. User Manual
Page 12

Publication 1738-IN021A-EN-E - January 2007
12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics
Environmental Specifications
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Damp Heat):
5-95% non-condensing
Shock
IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
Vibration
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
1V/m with 1 kHz sine-wave 80%AM from 2000 to 2700Mhz
EFT/B Immunity
IEC 61000-4-4:
±3kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions
CSPR 11:
Group 1, Class A
ArmorPoint 24V dc 4-channel Digital Input Module