Step 2: install the battery – Rockwell Automation 1794-FLA FlexLogix Controller Installation Instructions User Manual

Page 10

Advertising
background image

10 FlexLogix Controller System

Publication 1794-IN002G-EN-P - January 2004

Step 2: Install the Battery

For Safety information on the handling of lithium batteries, including handling and
disposal of leaking batteries, see Guidelines for Handling Lithium Batteries,
publication AG 5-4.

1. Install a 1756-BA1 battery.

2. Attach the battery label:

a. Write on the battery label the date you install the battery.

b. Attach the label to the inside of the battery compartment.

ATTENTION

Only install a 1756-BA1 battery. If you install a different battery,
you may damage the controller.

WARNING

For safety information on the handling of lithium batteries, in-
cluding the handling and disposal of leaking batteries, see Guide-
lines for Handling Lithium Batteries
, publication AG-5.4.
Store batteries in a cool, dry environment. We recommend 25

°C

with 40% to 60% relative humidity. You may store batteries for
up to 30 days between -45

° to 85°C, such as during transporta-

tion. To avoid possible leakage, do not store batteries above 60

°C

for more than 30 days.

When you connect or disconnect the battery an electrical arc can
occur. This could cause an explosion in hazardous location in-
stallations. Be sure that power is removed or the area is nonhaz-
ardous before proceeding.

Attach battery here.

top

red lead (+)

middle

black lead (-)

bottom

no connection

Attach label here.

This jumper is for service use
only. Do not use this jumper.

Advertising