4. Make sure power is not applied to the power supply.

5. Connect the power supply to the controller. The graphic below and its

related instructions describe a 1794-PS13 power supply.

a. Connect +24V dc input to the top of the controller connector, terminal A,

to the bottom, left power connector, terminal G.

b. Connect -24V common to top controller connector, terminal B, to the top,

left power connector, terminal E.

c. Use connections C and D on the controller and connection F and H on

the power supply to pass 24V dc power and common to the next module
in the series, if required.

Use the screw-terminal connector plug that comes with the controller to
meet the requirements for installations in Class I, Division 2 locations.

WARNING

If you connect or disconnect wiring while the field-side power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is re-
moved or the area is nonhazardous before proceeding.

+

+

A

B

C

D

F

E

H

G

_