Publication 1794-IN002G-EN-P - January 2004

Select the Operating Mode of the Controller

1. Use this table to determine the operating mode of the controller:

2. Turn the key on the front panel of the controller to select the mode.

If you want to:

Select one of these modes:

Run

Program

Remote

Run

Program

Test

turn outputs to the state commanded by
the logic of the project

YES

YES

turn outputs to their configured state for
Program mode

YES

YES

YES

execute (scan) tasks

YES

YES

YES

change the mode of the controller
through software

YES

YES

YES

download a project

YES

YES

schedule a ControlNet network

YES

YES

while online, edit the project

YES

YES

YES

YES

To select:

Turn the key to:

Remote Run

RUN and then to REM

Remote Program

PROG and then to REM

Remote Test

REM and then go online and select Test mode via the programming software

keyswitch

Advertising