FlexLogix Controller System 27

Publication 1794-IN002G-EN-P - January 2004

power supply

1794-PS3 or 1794-PS13 – In applications that must be compliant with CSA
requirements, use a Separated Extra-Low Voltage (SELV) power supply that is
compliant with IEC 61010.1, Annex H

power conductors

60° C (140° F) minimum, copper
#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded
3/64 inch (1.2mm) insulation maximum
length 10m or less

category 3

(2)

power connector torque

5 to 7 inch-pounds (0.6 to 0.8Nm)

battery

1756-BA1 (AB part number 94194801)
0.59g lithium

na

serial cable

1761-CBLPM02 to 1761-NET-AIC
1761-CBLPA00 to 1761-NET-AIC
1756-CP3 directly to controller
1747-CP3 directly to controller

category 3

(4)

na

extended local I/O cable

1794-CE1 cable (1 foot)
1794-CE3 cable (3 feet)

category 3

(2)

DIN rail

steel, 35 x 7.55mm DIN rail
A-B part number 199-DR1; 46277-3; EN 50022

operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)

storage temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

relative humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing

vibration

(3)

IEC60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz

shock

(3)

operating
non-operating

IEC60068-2-27: (Test Ea, Unpackaged shock):

30g
50g

emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges