FlexLogix Controller System 17

Publication 1794-IN002G-EN-P - January 2004

7. Connect the adapter to the controller.

The following diagram shows how you can also use the 1794-CE1, -CE3
cable to split a rail of I/O. You can split each rail only once. You can split a
rail right after the controller (or adapter) or after any I/O module. For more
information about the 1794-CE1, -CE3 cables, see the Interconnect Cable
Installation Instructions
, publication 1794-5.12.

Removing the extended-local adapter

If you need to remove the adapter, follow these steps:

1. Turn off power to the adapter.

2. Disconnect all cables from the adapter.

3. Remove the I/O module that is adjacent to the adapter.

4. On the terminal base adjacent to the adapter, slide the FLEXBUS connector

away from the adapter and remove the I/O terminal base.

5. Remove the adapter from the DIN rail.

31039-M

1794-CE1 or
1794-CE3 cable

LOCAL rail

LOCAL2 rail

1794-CE1 or
1794-CE3 cable

1794-CE1 or
1794-CE3 cable

1794-CE1 or
1794-CE3 cable