SLC™ 500 4-Channel Analog I/O Modules 15

Publication 1746-IN008C-EN-P - May 2004

4. At END 1, twist the drain wire and foil shield together, bend them away from

the cable, and apply shrink wrap.

5. At END 2, cut the drain wire and foil shield back to the cable and apply

shrink wrap.

6. Connect the signal wires (black and clear) to the terminal block and the

input and output devices. The recommended maximum torque is 0.57 Nm (5
lb-in) for all terminals.

Input channels - connect END 1 at module. Use a chassis mounting tab
as a ground for the drain wire and foil shield.

Output channel- connect END 2 at the module. Ground the drain wire
and foil shield at the analog load.

7. Repeat steps 1 through 6 for each channel on the analog module. Jumper

the unused plus (+), minus (-) and common terminals of each input channel
individually. Unused output and common terminals should be left
unconnected.

The following illustrations depict the proper cable preparation for END 1 and END
2. Shrink wrap is applied to each cable end. Make sure the foil shield and drain
wires on END 1 are long enough to reach their designated earth ground points.

Cable Preparation END 1

Foil Shield and
Drain Wire

Black Wire

Black Wire

Clear Wire

Clear Wire

Insulation

Insulation

Cable Preparation END 2