26 SLC™ 500 4-Channel Analog I/O Modules

Publication 1746-IN008C-EN-P - May 2004

Current Output Specifications for NIO4I, NO4I, and FIO4I

Description

Specification

NIO4I, NO4I

FIO4I

Converter Resolution

14 bit

Location of LSB in I/O image word

0000 0000 0000 01XX

Non–linearity

0.05%

Conversion Method

R-2R Ladder

Step Response

2.5 ms (at 95%)

Load Range

0 to 500 Ohms

Maximum Load Reactance

100 µH

Current Output Coding (0 to

+

21 mA - 1 LSB)

0 to +32764

Output Range (Normal)

0 to +20 mA

0 to +20 mA -1 LSB

Overrange Capability

5% (0 to +21 mA - 1 LSB)

5% (0 to +20 mA - 1 LSB)

Resolution

2.56348 µA per LSB

Full Scale

21 mA

Overall Accuracy at +25° C (77° F) (max.)

±0.298% of full scale

Overall Accuracy at 0° to +60° C

(32° to 140° F) (max.)

±0.541% of full scale

Overall Accuracy Drift (max.)

±70ppm/° C of full scale

Gain Error at +25° C (77° F) (max.)

±0.298%

Gain Error at 0° to +60° C (32° to 140° F) (max.)

±0.516%

Gain Error Drift (max.)

±62ppm/° C

Offset Error at +25° C (77° F) (max.)

±10 LSB

Offset Error at 0° to +60° C (32° to 140° F) (max.) ±12 LSB

Offset Error Drift (max.)

±0.06 LSB/° C

@JO$&/QQE

@JO$&/QQE

".

".