Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules Installation Instructions User Manual

Page 8

Advertising
background image

8 SLC™ 500 4-Channel Analog I/O Modules

Publication 1746-IN008C-EN-P - May 2004

Determining Your Power Requirements for a Modular Controller

Analog modules require both 5V dc and 24V dc power from the backplane of the
SLC 500 system. However, the NO4I and NO4V analog modules can use an external
24V dc power supply. This eliminates the 24V dc backplane power requirements,
providing configuration flexibility if SLC power supply loading is critical. These two
modules provide user-supplied external 24V dc power supply connections.

The following table shows the power requirements for each analog module using
backplane power. Use this table to calculate the total load on the modular system
power supply. For more information refer to the SLC 500 Modular Hardware Style
User Manual
, publication 1747-UM011.

Determining Your Power Requirements for a Fixed Controller

IMPORTANT

The analog modules do not supply loop power for the input
device. You must supply the appropriate loop power for
loop-powered input devices.

Catalog Number

5 Volt Current

24 Volt Current

1746-NI4

35 mA

85 mA

1746-NIO4I

55 mA

145 mA

1746-NIO4V

55 mA

115 mA

1746-NO4I

55 mA

195 mA

(1)

(2)

(1)

The 24V dc user power connection on a fixed SLC 500 can power an NO4I or NO4V analog module. However, the regulation
of the 24V dc user connection on a modular SLC 500 power supply, catalog number 1746-P1, -P2, and -P4 is outside of the
requirements of the NO4I and NO4V analog modules and cannot be used.

(2)

Omit these values from your SLC power supply loading calculations if you decide to use an external power supply.

1746-NO4V

55 mA

145 mA

(1)

(2)

1746-FIO4I

55 mA

150 mA

1746-FIO4V

55 mA

120 mA

IMPORTANT

The 2-slot, SLC 500 fixed I/O expansion chassis (1746-A2) will
support only specific combinations of modules. If you wish to
use an I/O module in a 2-slot expansion chassis with another
SLC I/O or communication module, refer to the SLC 500
Analog I/O Modules User Manual
, publication 1746-UM005 for
valid combinations of modules.