Analog modules operation – Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules Installation Instructions User Manual

Page 5

Advertising
background image

SLC™ 500 4-Channel Analog I/O Modules 5

Publication 1746-IN008C-EN-P - May 2004

Analog Modules Operation

The module converts analog input signals to 16-bit binary values for storage in the
SLC processor’s input image table. The decimal range, number of significant bits,
and converter resolution depend on the input range that you use for the channel.

Analog Input A/D Characteristics

Analog Output D/A Characteristics

The analog modules have the same output characteristics.

NI4, NIO4I, & NIO4V Input
Range

Decimal Range (input
image table)

Number of
Significant Bits

Nominal Resolution

±10V dc -1 LSB

-32,768 to +32,767

16

305.176 µV/LSB

0 to 10V dc -1 LSB

0 to 32,767

15

0 to 5V dc

0 to 16,384

14

1 to 5V dc

3,277 to 16,384

13.67

±20 mA

±16,384

15

1.22070 µA/LSB

0 to 20 mA

0 to 16,384

14

4 to 20 mA

3,277 to 16,384

13.67

FIO4I and FIO4V Input
Range

Decimal Range (input
image table)

Number of
Significant Bits

Nominal Resolution

0 to 10V dc -1 LSB

0 to 4095

12

2.4414 mV/LSB

0 to 5V dc

0 to 2047

11

1 to 5V dc

409 to 2047

10.67

0 to 20 mA

0 to 2047

11

9.7656 µA/LSB

4 to 20 mA

409 to 2047

10.67

Module

Output Range

Decimal Range (output
image table)

Significant Bits Resolution

FIO4I

NIO4I

NO4I

0 to 21 mA - 1 LSB

0 to 32,764

13 bits

2.56348 µA/LSB

0 to 20 mA

0 to 31,208

12.92 bits

4 to 20 mA

6,242 to 31,2089

12.6 bits

FIO4V

NIO4V

NO4V

±10V dc - 1 LSB

-32,768 to +32,764

14 bits

1.22070 mV/LSB

0 to 10V dc -1 LSB

0 to 32,764

13 bits

0 to 5V dc

0 to 16,384

12 bits

1 to 5V dc

3,277 to 16,384

11.67 bits

@JO$&/QQE

@JO$&/QQE

".

".

Advertising